DS7400Xi-AT (Ver. 3+) Reference Guide Copyright © 1995-2000 Detection Systems, Inc. Page 71
Grade C using Digital Alarm
Communicator Transmitter
only.
The controls must be installed in accordance with U. L. Standards
UL681 and UL609 for all grades of service.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 0325) must be
programmed.
• AC Failure Report (Program Address 0327) must be programmed.
• Open Report (Program Address 0320) must be programmed.
• Close Report (Program Address 0321) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 0329 and 0336)
must be programmed.
2. General Control Programming:
• The control must not be programmed for auto disarm.
• Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
• Program Address 0185 must be programmed as: Data Digit 1=0,
Data Digit 2=0.
3. Zone Function Programming:
• The Burglar alarm signal (whether pulsed or steady) must be
different from the Fire alarm signal.
4. Alarm Output Programming:
• Program Address 0146 must be programmed as: Data Digit 1=6,
Data Digit 2=3.
• Program Address 0149 must be programmed as: Data Digit 1=8.
12.4.1 Local Burglary Alarm
A. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• An Ademco Model AB-12 bell/housing (see section 12.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 0195 and 0196) must be
programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
12.4.2 Police Station Connection
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• An ARDIS (or DataTAC) interface module.
• The ARDIS module and antenna should be mounted within the
protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
B. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be the Detection System’s model DS7400XiCC
with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 12.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 0195 and 0196) must be
programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
12.4.3 Central Station Burglary Alarm and Proprietary
A. Central Station Burglary Grades AA and A and Proprietary
Grade AA Installations using an ARDIS Interface Module
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• An ARDIS (or DataTAC) interface module.
• The ARDIS module and antenna should be mounted within the
protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
• The Ademco Model AB-12 bell/housing (see section 12.6).
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
B. Grade B Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 12.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 0195 and 0196) must be
programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
C. Central Station Burglary Grade C and Proprietary Grade A
Installations using Digital Alarm Communicator Transmitter only
Follow General System Requirements as listed in 12.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 0191-0193) must
be programmed for not longer than 60 seconds.
12.5
Commercial Fire Alarm
A. Central Station (DACT) and Local
The control must be installed in accordance with NFPA 72.
Required Accessories:
• DS7420i Dual Phone Line/Bell Supervision Module.
• For Local Commercial Fire Alarm: A Listed notification appliance
such as a Wheelock 46T-G10-12 bell or 34T-12 horn.
• If not using the phone line supervision, it must be disabled.
• AE-TR16 Transformer Housing.
• At least one DS7447 must be used and assigned as keypad 1. If
only one is used, it may be connected to the keypad bus if the
keypad is mounted to the front of the box or within the same room
as the control equipment and the wire is run in conduit (or
equivalently protected against mechanical injury) within 20 ft.
(6.1 m) of the control equipment. If multiple keypads are used,
one keypad only must be used on the options bus and assigned