background image

16

106573

DIRECT-VENT GAS FIREPLACE

EVDDVF36PN and EVDDVF36STN

®

INSTALLATION

INSTALLING OPTIONAL
WALL MOUNT SWITCH
GWMS2

NOTICE: The GWMS2 includes
25' of wire for installation. Your
fireplace includes 15' of wire for
accessory installation. Choose the
length that best fits your needs
when installing this accessory.

The installation of a wall switch allows you
to activate the gas control valve and turn
the fireplace on and off. The wall switch is
to be connected to the incoming 120 volt
regular household wiring that supplies elec-
tricity to the fireplace. Refer to wiring
diagram on page 22.

For Optional
Fan Kit

From Blower
Assembly

 CAUTION: Due to high tem-

peratures, make sure no wires
are touching the bottom of the
firebox.

OPTIONAL BLOWER
ASSEMBLY INSTALLATION

Before blower assembly can be operated, it
must be properly connected to a standard
120 VAC power source. Refer to Wiring
Diagram
 on page 22.

1.

To remove lower louver, pull both top
spring latches toward the center of the
appliance at the same time until they
are disengaged from the locating holes.
Repeat for bottom spring latches and
pull louver outward.

2.

Place blower assembly so it rests flush
against the inside wall on the flue exit
side of the firebox (see Figure 32).
There are four magnets on the bottom
of the blower assembly that will keep
the blower in place on firebox bottom.

Note:

 If the blower kit is not installed

flush against the inside side wall of the
fireplace, the circulating air from the
blower system will not flow properly.

 WARNING: Disconnect all

electrical power to the fireplace.
Be careful of burrs and sharp
edges.

BLOWER SPEED CONTROL
INSTALLATION

1.

Place speed control switch assembly on
the bottom of the inside of the firebox
(see Figure 33). The assembly is
equipped with magnets on the left and
right to properly anchor it to the firebox.

2.

Plug blower with speed control assem-
bly into a power source. Keep hands
clear of fan when running. 

Note:

 An

outlet box with two receptacles has been
supplied for your convenience, located
on the lower left side of the appliance
(see Figure 34). An optional remote
control may be installed at any time.

Figure 32 - Blower Assembly Placement

Blower
Assembly

Blower Center to
Firebox Bottom
Center Along Inside
Wall by Flue Exit

Peninsula
or See-Thru
Fireplace
Installed

Flue
Exit

Inside
Wall

BLOWER SPEED CONTROL
OPERATION

1.

To operate blower, turn the blower speed
control knob clockwise to the “on” po-
sition (see Figure 36). This will be the
highest blower speed. Continue turning
knob clockwise to reduce blower speed.
Turn knob only within the specified
range (1/4 revolution, see Figure 36).

2.

To turn blower off, turn blower speed
control knob counter-clockwise until it
clicks into the “off” position. You must
turn until knob clicks for the unit to be
completely off.

Figure 34 - Connecting Blower Accessory
to Power Supply

Figure 33 - Blower Speed Control Location

Glass

Speed Control

Spring
Latch

BLOWER
SPEED
CONTROL

BLOWER
ASSEMBLY

BLK (16 ga.)

BLK (16 ga.)

Wire Connectors
3 Places

Figure 35 - Wiring Diagram for Blower
Assembly

Magnet

High Speed
ON/OFF

Low
Speed

Magnets

1/4 Revolution

Figure 36 - Blower Speed Control

Summary of Contents for Vanguard EVDDVF36PN

Page 1: ...gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier SAVE...

Page 2: ...d Back of Surround Figure 2 EVDDVF36STN See Thru Dimensions Left Side Surround Right Side Surround Rating Plate Location Left Side Surround Right Side Surround GLOSSARY OF TERMS Chase A box like enclo...

Page 3: ...gas approved for use in this gas appliance NOTICE Check local building codes for area requirements be fore installing this appliance This appliance when installed must be elec trically grounded in ac...

Page 4: ...ock re quired air spaces with insula tion or any other material Do not obstruct the effective opening of the appliance with any type of facing material MANTEL CLEARANCES Woodwork such as wood trims ma...

Page 5: ...ting terminals into a wall or siding If installing on vinyl siding a vinyl sid ing standoff must be used see Figure 19 page 9 Install horizontal venting with a 1 4 rise for every 12 of run toward the...

Page 6: ...aved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum of 2...

Page 7: ...t is important to select the proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical...

Page 8: ...the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lugs will slide strai...

Page 9: ...of the vent cap Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained...

Page 10: ...al V and Horizontal H maxi mums and minimums The same amounts apply for flexible venting FGFVK Vent Kit Shown Horizontal Termination Configurations Figures 21 through 23 show different con figurations...

Page 11: ...90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 4 max 6 min 8 max 7 min 10 max 8 min 15 max 20 max 20 max Figure 23 Horizontal Termination Configuration for Rigid Venting Using Two 90 Elbows w...

Page 12: ...ances air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do not pack air spaces with insulation Also note maxi mum vertical rise of the venting sys tem a...

Page 13: ...ort box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the supportbox from the top corne...

Page 14: ...tion With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 20 max Fi...

Page 15: ...shing RTV Silicone Vertical Termination and 26 screws D1000 7 x 12 Galvanized Coaxial Pipe 6 pcs D1010 7 x 24 Galvanized Coaxial Pipe 6 pcs D1020 7 x 48 Galvanized Coaxial Pipe 6 pcs D1030 7 Adjustabl...

Page 16: ...he blower system will not flow properly WARNING Disconnect all electrical power to the fireplace Be careful of burrs and sharp edges BLOWER SPEED CONTROL INSTALLATION 1 Place speed control switch asse...

Page 17: ...em at test pressures equal to or less than 1 2 psig 3 5 kPa 1 Install a sediment trap between the in coming gas line and the gas control valve see Figure 40 The sediment trap should extend down the ce...

Page 18: ...to prevent damage to glass or refractory 1 Remove top and bottom louvers by si multaneously pulling both top end spring latches towards the center of the applianceuntiltheyaredisengagedfrom locating...

Page 19: ...d during shipping and han dling If this is the case some minor adjust ments may be necessary and should be done by a qualified technician To access the elec trode the glass door must be opened The pro...

Page 20: ...ng ignition Young children should be carefully supervised when they are in the same room as the appliance WARNING Have a qualified agency periodically inspect the vent system at the start of each heat...

Page 21: ...tes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety in formation in column one If you don t smell gas go to the next step 7 Turnequipments...

Page 22: ...iginalreplacementpart s call DESA International s Technical Ser vice Department at 1 800 323 5190 for re ferral information When calling DESA International have ready your name your address model and...

Page 23: ...Replace control valve see Replacement Parts page 27 5 Tighten wires or replace electrode 6 Check that the main power is on and that all wire connections are made correctly to the ignition module see W...

Page 24: ...oved from line Have gas line checked by local pro pane LP gas company 2 Clean burner or replace burner orifice 1 Adjust the log set so that the flame does not excessively impinge on it 2 Inspect the o...

Page 25: ...ss too loose and air tight gasket leaks in corners after usage 6 Improper vent cap installation 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Bu...

Page 26: ...overplate andmillivoltwires are supplied with the appliance If wires need replacing use proper gauge Millivolt Wires Wall Switch and Cover Plate ORIFICE Natural 105890 01 27224 REPLACEMENT PARTS A A B...

Page 27: ...PARTS Continued Front Bottom Left Right Bottom Front Used for See Thru Only GRATE 105889 01 11184 DOOR ASSEMBLY Tempered 106923 01 27200 LOUVER KIT Black 105904 01 01627 END LOUVER KIT Peninsula Only...

Page 28: ...l be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIE...

Reviews: