72
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47017
7016
Volts Line to Line Avg
Average of the system line to line voltages.
47018
7017
Volts Line to Neutral Avg
Average of the system line to neutral voltages.
47019
7018
Volts L1 to L2
Individual phase to phase voltages.
47020
7019
Volts L2 to L3
“
47021
7020
Volts L3 to L1
“
47022
7021
Measured Line Frequency
Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.
47023
7022
Negative kWh L1 LSW
Individual Phase Negative True Energy LSW (kWh,
resettable)
47024
7023
Negative kWh L1 MSW
Individual Phase Negative True Energy MSW (kWh,
resettable)
47025
7024
Negative kWh L2 LSW
“
47026
7025
Negative kWh L2 MSW
“
47027
7026
Negative kWh L3 LSW
“
47028
7027
Negative kWh L3 MSW
“
47029
7028
Negative kW L1
Individual Phase Instantaneous Negative True Powers
(kW)
47030
7029
Negative kW L2
“
47031
7030
Negative kW L3
“
47032
7031
Negative kVARh L1 LSW
Individual Phase Negative Reactive Energy LSW