45
CT
W
IRE
L
EAD
P
OLARITY
CT Type
CT Lead +
CT Lead -
Rogowski (R
ō
Coil)*
White
Brown
Split Core mV
White
Black
Clamp On mV
Red
Black
Table III-4: CT Polarity
NOTE:
The directionality for Rogowski CTs is the arrow points toward the load (e.g. motor).
* R
ōCoils
have a shield wire which must be connected to the meter. This reduces interference and
improves accuracy of the CT.
Connecting Voltage
1) Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter. A voltage lead of
14 AWG
THHN Minimum 600VAC rating
(or equivalent in order to maintain 600VAC safety rating of the
device) is required.
2) Connect the leads to the circuit breaker.
a) Refer to the wiring diagrams in for wiring
connection specifics. Follow local electrical codes
during this installation.
b)
IMPORTANT:
Verify the breaker is marked as the
disconnect breaker for the meter.
D
ID
Y
OU
K
NOW
?
The PowerScout is rated
for 600V Over-Voltage Category III.
Cat III is for measurements performed in
the building. Examples are
measurements on distribution boards,
circuit-breakers, wiring including cables,
bus bars, junction boxes, switches, and
socket outlets in a fixed installation, and
equipment for industrial use. Other
equipment could include stationary
motors with a permanent connection to
the fixed installation.