65
Modbus
Offset
Register
Description
* System=sum of three phases
44046
4045
kVAh L3 MSW
“
44047
4046
kVA L1
Individual Phase Apparent Powers (kVA)
44048
4047
kVA L2
“
44049
4048
kVA L3
“
44050
4049
Displacement PF L1
Individual Phase displacement Power Factor (PF)
44051
4050
Displacement PF L2
“
44052
4051
Displacement PF L3
“
44053
4052
Apparent PF L1
Individual Phase apparent Power Factors (PF)
44054
4053
Apparent PF L2
“
44055
4054
Apparent PF L3
“
44056
4055
Amps L1
Individual Phase Currents (A)
44057
4056
Amps L2
“
44058
4057
Amps L3
“
44059
4058
Volts L1 to Neutral
Individual Phase to Neutral Voltages (V)
44060
4059
Volts L2 to Neutral
“
44061
4060
Volts L3 to Neutral
“
44062
4061
Time Since Reset LSW
Seconds since KWH register was reset. LSW
44063
4062
Time Since Reset MSW
Seconds since KWH register was reset. MSW
44064
4063
Data Tick Counter
Internal sample count (gets cleared every minute):
may be used to determine if sample read is a newer
sample than last read.
44080
4079
kW System Average
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable)
44081
4080
kW Demand System Min
System Minimum Demand (kW)