![DENT Instruments powerscout 3037 Operator'S Manual Download Page 34](http://html.mh-extra.com/html/dent-instruments/powerscout-3037/powerscout-3037_operators-manual_2483355034.webp)
35
Changing the PowerScout from
Modbus to BACnet mode:
1) Connect to the PowerScout using ViewPoint.
2) Go to the Read/Write Registers tab in ViewPoint.
3) Enter
44612
into the
Register
field or click
List
to select from the
Register Picker List.
4) In the
Value
field, enter
1833
to change to BACnet mode.
5) Click
OK
.
The status should say “Writing Value…”
Return to the Communications tab and connect.
Changing the PowerScout from
BACnet to Modbus mode:
1) Connect to the PowerScout using ViewPoint.
2) Go to the Read/Set Objects tab in ViewPoint.
3) Enter
10190
into the
Object
field or click
List
to select from the Object Picker List.
4) In the
Value
field, enter
375
to change to Modbus mode.
5) Click
OK
.
The status should say “Writing Value…”
Return to the Communications tab and connect.