16
following a post purge of 30 seconds and a safe start check. Failure to ignition spark on the second
attempt results in safety lockout.
MEP100P
The MEP100P programmers provides a fixed 15 second post purge period upon detection of the
operating Control (1-7) or Air Flow switch (7-6) opening.
MEP100 as FLAME SWITCH (refer to Figure 11)
For systems that require flame switch operation, that is, relay KF will toggle on with flame signal
and off without flame signal, the MicroM provides this function when equipped with an MEP100
programmer. To operate as a flame switch, Terminals 1 and 6
MUST
be powered with 120 VAC
while Terminal 7
MUST
be left unpowered. Terminals 3, 4, and 5 will provide an isolated (KL relay
not energized) set of contacts with Terminal 3 being the common input, Terminal 4 will be normally
closed and Terminal 5 will be normally open.
If Terminal 7 is powered or if Terminal 6 is non-
powered and a flame signal is present, the MicroM will lockout after 1 minute and Terminals 4
and 5 will no longer switch with flame signal.
Refer to Figure 11 for configuration wiring. Air
Flow LED will blink while flame is detected.
TIMING CHART
Terminal #5 is energized 3 seconds after flame is detected.
Re-ignited PTFI on flame fail after Terminal 5 energized.
Recycle on loss of interlock (air flow) after flame proven.
MEP101
Same as MEP100 but will tolerate flame signal during “Off” cycle.
MEP102
PTFI time limited to 5 seconds, lockout on flame fail.
MEP104
PTFI time limited to 10 seconds, lockout on flame fail.
MEP200 SERIES
The MEP200 Series programmers come equipped with a bank of dipswitches that allow user select-
able prepurge timing, selectable PTFI timing, selectable post purge, selectable air flow proven open
at start, and selectable recycle/non-recycle operation. Refer to PROGRAMMER DIPSWITCH SET-
TINGS for detailed information.
Recycle operation refers to flame failure during the main (AUTO) firing period. In the event of a
main flame failure, power is removed from Terminal 3 and Terminal 5. If selected by the dipswitch,
the control will enter a post purge period for 15 seconds and revert back to the Idle state where the
pre-purge period begins.
TYPE MEP100
PROGRAMMING SEQUENCE
L1/7
ON
INTERLOCK
AIR FLOW
PROVEN
FIRING
PERIOD
L1/7
OFF
PTFI
10 SEC
SAFE
START
CHECK
PERIOD
8
T
E
R
M
I
N
A
L
S
3
4
5
Summary of Contents for MOISTURE Link G2 DP
Page 1: ...Operation Manual 2019 MODELS MSF DP DPSL DPXSL DPX4T DPX8T DPX12T DPX16GT Grain Dryer Controls...
Page 2: ......
Page 4: ...2...
Page 7: ...GENERAL INSTRUCTIONS 3 5...
Page 153: ...151...
Page 154: ...152...
Page 166: ...164...
Page 190: ...188...
Page 200: ...198...
Page 201: ...199...
Page 202: ...200...
Page 203: ...201...
Page 204: ...202...
Page 205: ...203...
Page 206: ...204...
Page 207: ...205...
Page 208: ...206...
Page 209: ...207...
Page 210: ...208...
Page 211: ...209...
Page 212: ...210...
Page 213: ...211...
Page 214: ...212...
Page 215: ...213...
Page 216: ...214...
Page 217: ...215...
Page 218: ...216...
Page 219: ...217...
Page 220: ...218...
Page 221: ...219...
Page 222: ...220...
Page 223: ...221...
Page 224: ...222...
Page 225: ...223...
Page 226: ...224...
Page 227: ...225...
Page 228: ...226...
Page 229: ...227...
Page 242: ...240...
Page 243: ...241...
Page 244: ...242...
Page 245: ...243...
Page 301: ...56 FIGURE 19 Red jumper wire Red wire...
Page 302: ...57...
Page 310: ...2011 Service Manual Rev A 282...
Page 311: ...2011 Service Manual Rev A 283...
Page 312: ...2011 Service Manual Rev A 284...
Page 313: ...2011 Service Manual Rev A 285...
Page 314: ...2011 Service Manual Rev A 286...
Page 315: ...2011 Service Manual Rev A 287...
Page 316: ...2011 Service Manual Rev A 288...
Page 317: ...2011 Service Manual Rev A 289...
Page 318: ...2011 Service Manual Rev A 290...
Page 319: ...2011 Service Manual Rev A 291...
Page 320: ...2011 Service Manual Rev A 292...
Page 321: ...2011 Service Manual Rev A 293...
Page 322: ...2011 Service Manual Rev A 294...