By pressing the OK key, the submenu can be reached and the
parameter value shown can be changed.
Please note: The changed values must be confirmed after
entering by a press of the OK key.
PROP-BAND
10,0 °C
Proportional range
Setting the proprotional range of the PID conroller. The
proportion functions in a way that the correcting variable is
linearly reduced from +/-100% to 0% when the actual value
nears the set point.
T HIGH DIFF
3 °C
T LOW DIFF
-3 °C
Maximum temperature deviation of difference regulation. If the
temperature deviation of the flow temperature from the zone
temperature is larger than the set value, the alarm output D06
is activated and the symbol H appears in the display.
I-ANTEIL
100 sec
D-ANTEIL
20 sec
Integral proportion factor
Setting the I and D proportions of the PID regulator. When the
setting is 0, the values are invalid
Setting parameter for the differential proportion
see integral proportion
Minimum temperature deviation of difference regulation. If the
temperature deviation of the flow temperature from the zone
temperature is larger than the set value, the alarm output D06
is activated and the symbol L appears in the display.
T HIGH MIN
25,0 °C
T LOW MIN
0,0 °C
Minimum limit temperature at low temperatures.
If the flow temperature is colder than the set value, the alarm
output D06 is activated and the symbol L appears in the
display.
T HIGH MAX
45,0 °C
Maximum limit temperature at high temperatures.
If the flow temperature is warmer than the set value, the alarm
output D06 is activated and the symbol H appears in the
display.
Minimum limit temperature at high temperatures.
If the flow temperature is colder than the set value, the alarm
output D06 is activated and the symbol L appears in the
display.