Group 3 Output Function Parameters
Parameter
Function
Setting
Default Customer
03.00
Multi-function Output
Relay (RA1, RB1,
RC1)
0: No function
1: Indication during RUN
2: Indication of master frequency reached
8
3: Zero speed
4: Over-torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
7: Operation mode indication
8: Fault indication
9: Desired frequency reached
10: Terminal count value reached
11: Preliminary count value reached
12: Over-voltage stall prevention
13: Over-current Stall prevention
14: IGBT overheat warning
(85
°
C: ON, 80
°
C: OFF)
15: Over-voltage
16: PID feedback error
17: Forward command
18: Reverse command
19: Zero speed output signal
20: Warning
21: Mechanical brake control (Desired frequency
reached)
22: Drive ready
23: Multi-pump system error display (only master)
24: Preheating function indication
25: Fire mode indication
03.02
Desired Frequency
Reached
0.00–400.0 Hz
0.00
03.05
Terminal Count Value 0–9999
0
03.06
Preliminary Count
Value
0–9999
0
03.07
EF Active when
Terminal Count Value
Reached
0: Terminal count value reached, no EF display
0
1: Terminal count value reached, EF active
03.08
Fan Control
0: Fan is always ON
0
1: One minute after the AC motor drive stops, the fan
is OFF.
2: Fan is ON when the AC motor drive runs, fan is
OFF when the AC motor drive stops.
3: Fan is ON when the preliminary heat sink
temperature is reached.
4: Fan is ON when the AC motor drive runs; fan is
OFF when the AC motor drive stops. And the fan
is in a standby mode at 0 Hz.
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...