Chapter 4 Parameters
VFD-EL-W
4-100
Parameter
Function
Setting
s
Default
End
user’s
master
End
user’s
slave
Note
10.00
PID Set Point
Selection
0: Disable
1: Digital keypad UP/DOWN
keys
2: Reserved
3: Reserved
4: PID set point (Pr.10.11)
0
1
1
Adjusts according
to customer’s
applications
10.01
Input Terminal for
PID Feedback
0: Positive PID feedback from
external terminal AVI
(0–10 V
DC
)
1: Negative PID feedback from
external terminal AVI
(0–10 V
DC
)
2: Positive PID feedback from
external terminal ACI
(4–20 mA)
3: Negative PID feedback from
external terminal ACI
(4–20 mA)
0
3
3
10.02
Proportional Gain
(P)
0.0–10.0
1.0
1.2
1.2
Adjusts according
to customer’s
applications
10.03
Integral Time (I)
0.00–100.00 sec.
(0.00=Disable)
1.00
0.7
0.7
10.04
Differential Time (D) 0.00–1.00 sec.
0.00
-
-
10.12
PID Deviation Level 0.0–100.0%
10.0
5
5
When the
pressure feedback
is < 0.5 kg and
time > 15 sec.,
follow the settings
for Pr.10.20.
10.13
PID Deviation
Detection Time
0.1–300.0 sec.
5.0
15
15
10.18
Feedback of PID
Physical Quantity
Value
1.0–99.9
99.9
10
10
Sets the maximum
feedback of PID
physical quantity
value to be 10 kg.
10.19
PID Calculation
Mode Selection
0: Serial mode
1: Parallel mode
0
1
1
The parallel PID
calculation mode
applies for the
constant pressure
water supply
control.
10.20
Erroneous PID
Feedback Deviation
Level Action
0: Wan and keep operating
1: Warn and coast to stop
2: Warn and ramp to stop
3: Ramp to stop and restart
after Pr.10.21 delay time
0
3
3
When there is
water shortage or
unusual pressure
feedback, the
pump stops
running for 1800
sec. (30 minutes)
until the pressure
feedback is back
to normal.
10.21
Restart Delay Time
after Erroneous PID
Deviation Level
0–9999 sec.
60
1800
1800
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...