10.35
Multi-pump Control
Mode
0: Disable
1: Fixed time circulation
(alternative operation)
2: Fixed quantity control
(multi-pump operating at
constant pressure)
0
1
1
10.36
Multi-pump ID
0: Multi-pump control mode is
disabled
1: Master
2–4: Slave
0
1
2
10.37
Multi-pump’s Fixed
Time Circulation
Period
1–65535 minutes
60
1
1
10.42 Pump’s Frequency at
Time-out
(Disconnection)
0.00 Hz–FMAX
0.00
60
60
10.43
Pump’s Error
Treatment
Bit0: Determines whether the
erroneous pump switches to an
alternative pump when an error
occurs in the running pump.
0: All pumps stop.
1: Switch to an alternative pump
Bit1: Determines the erroneous
pump to be in a standby or stop
status after reset.
0: Standby after reset.
1: Stop after reset.
Bit2: Determines whether the
master pump receives the RUN
command or not when an error
occurs in the running pump.
0: Does not receives the RUN
command.
1: Choose to run with an
alternative pump.
1
1
1
000=0
001=1
010=2
011=3
100=4
101=5
110=6
111=7
10.44
Selection of Pump’s
Start-up Sequence
0: By pump ID#
1: By running time
0
1
1
Adjusts according
to customer’s
applications
10.45
Running Time of
Multi-pump Under
Alternative Operation
0.0–360.0 sec.
60.0
60.0
60.0
Adjusts according
to customer’s
applications
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...