Chapter 4 Parameters
VFD-EL-W
4-4
Group 1 Basic Parameters
Parameter
Function
Setting
Default Customer
01.00
Maximum Output Frequency (Fmax)
50.00–400.0 Hz
60.00
01.01
Motor Rated Frequency (Fbase)
0.10–400.0 Hz
60.00
01.02
Motor Rated Voltage (Vbase)
230V series: 0.1–255.0 V
220.0
460V series: 0.1–510.0 V
440.0
01.03
Mid-Point Frequency (Fmid)
0.10–400.0 Hz
1.50
01.04
Mid-Point Voltage (Vmid)
230V series: 0.1–255.0 V
10.0
460V series: 0.1–510.0 V
20.0
01.05
Minimum Output Frequency (Fmin)
0.10–400.00 Hz
1.50
01.06
Minimum Output Voltage (Vmin)
230V series: 0.1–255.0 V
10.0
460V series: 0.1–510.0 V
20.0
01.07
Output Frequency Upper Limit
0.1–120.0%
110.0
01.08
Output Frequency Lower Limit
0.0–100.0 %
0.0
01.09 Acceleration Time 1 (Taccel 1)
0.1–600.0 / 0.01–600.00 sec.
10.0
01.10 Deceleration Time 1 (Tdecel 1)
0.1–600.0 / 0.01–600.00 sec.
10.0
01.11 Acceleration Time 2 (Taccel 2)
0.1–600.0 / 0.01–600.00 sec.
10.0
01.12 Deceleration Time 2 (Tdecel 2)
0.1–600.0 / 0.01–600.00 sec.
10.0
01.13 Jog Acceleration Time
0.1–600.0 / 0.01–600.00 sec.
1.0
01.14 Jog Deceleration Time
0.1–600.0 / 0.01–600.00 sec.
1.0
01.15 Jog Frequency
0.10–400.0 Hz
6.00
01.16
Auto-Acceleration and
Auto-Deceleration
0: Linear Acceleration and linear
deceleration
0
1: Auto-acceleration and linear
deceleration
2: Linear acceleration and auto-
deceleration
3: Auto-acceleration and auto-
deceleration (Set by load)
4: Auto-acceleration and auto-
deceleration (set by Acceleration
/ Deceleration Time setting)
01.17
Acceleration S-Curve
0.0 (S-curve disabled)
0.1–10.0 / 0.01–10.00
[S-curve enabled (10.0/10.00 is the
smoothest)]
0.0 / 0.00
01.18
Deceleration S-Curve
01.19
Acceleration / Deceleration Time Unit
0: Unit: 0.1 sec.
0
1: Unit: 0.01 sec.
01.20 Simple Positioning Stop Frequency 0
0.00–400.0 Hz
0.00
01.21 Simple Positioning Stop Frequency 1
5.00
01.22 Simple Positioning Stop Frequency 2
10.00
01.23 Simple Positioning Stop Frequency 3
20.00
01.24 Simple Positioning Stop Frequency 4
30.00
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...