Appendix A Specifications
VFD-EL-W
A-3
A3. General Specifications
Characteristics
Descriptions
C
o
nt
ro
l C
h
a
ra
ct
e
ris
tic
s
Control System
SPWM (Sinusoidal Pulse Width Modulation) control (V/F control, Vector
Control)
Frequency Setting Resolution 0.01 Hz
Output Frequency Resolution 0.01 Hz
Torque Characteristics
Includes the auto-torque/auto-slip compensation; starting torque can be
150% at 5.0 Hz
Overload Tolerance
150% of rated current for one minute
Skip Frequency
Three zones, setting range 0.1–400 Hz
Accel/Decel Time
0.1–600 seconds (2 Independent settings for Accel./ Decel. time)
Stall Prevention Level
Setting 20–250% of rated current
DC Brake
Operation frequency 0.1–400.0 Hz, output 0–100% rated current
Start time 0–60 seconds, stop time 0–60 seconds
V/F Pattern
Adjustable V/F pattern
O
p
er
at
in
g
C
ha
ra
ct
e
ri
st
ic
s
Frequency
Setting
Keypad
Setting by
External Signal Potentiometer-5 k
/ 0.5 W, 0–10 V
DC
, 4–20 mA, RS-485 interface; Multi-
function inputs 2 to 4 (7 steps, Jog, up/down)
Operation
Setting
Signal
Keypad
Set by RUN and STOP
External Signal
Single-wire (default setting MI1) or Two-wire/Three-wire (MI1, MI2, MI3) by
setting parameters, JOG operation, RS-485 serial interface (Modbus).
Multi-function Input Signal
Multi-step selection 0–7, Jog, accel./decel. inhibit, two accel./decel.
switches, counter, external Base Block, ACI/AVI selections, drive reset,
UP/DOWN key settings, NPN/PNP input selection
Multi-function Output
Indication
AC drive operating, frequency reached, zero speed, Base Block, fault
indication, overheat alarm, emergency stop and status selections for input
terminals.
Analog Output Signal
Output frequency/current
Operation Functions
AVR, accel./decel. S-Curve, over-voltage/over-current stall prevention, five
fault records, reverse inhibition, momentary power loss restart, DC brake,
auto-torque/slip compensation, auto-tuning, adjustable carrier frequency,
output frequency limits, parameter lock/reset, PID control, external counter,
Modbus communication, abnormality reset, abnormality restart, power-
saving, fan control, sleep/wake frequency, first/second frequency source
selections, first/second frequency source combination, NPN/PNP selection.
Protection Functions
Over-voltage, over-current, under-voltage, external fault, overload, ground
fault, overheating, electronic thermal, IGBT short circuit, PTC
Display Keypad
Six-key, seven-segment LED with four-digits, four status LEDs, master
frequency, output frequency, output current, custom units, parameter
values for setup and lock, faults, RUN, STOP, RESET, FWD/REV.
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...