![Delta VFD-EL-W Series User Manual Download Page 29](http://html.mh-extra.com/html/delta/vfd-el-w-series/vfd-el-w-series_user-manual_2471889029.webp)
Chapter 2 Installation and Wiring
VFD-EL-W
2-8
2.3.2 Main Circuit Terminals
Frame A1
Frame A2
Frame B
Frame
Model
Main Circuit Terminals
R/L1, S/L2, T/L3,U/T1, V/T2, W/T3,
Maximum
Wire
Gauge
Minimum
Wire
Gauge
Screw Size
Tightening
Torque (±10%)
A1
VFD002EL21W(-1)
4 mm
2
[12 AWG]
2.5 mm
2
[14 AWG]
M4 screw
15 kgf-cm
[13 lbf-in]
[1.47 N-m]
VFD004EL21W(-1)
VFD004EL43W(-1)
VFD007EL21W(-1)
4 mm
2
[12 AWG]
VFD007EL43W(-1)
2.5 mm
2
[14 AWG]
A2
VFD015EL43W(-1)
B
VFD015EL21W(-1)
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4 screw
13 kgf-cm
[11.4 lbf-in]
[1.3 N-m]
VFD022EL21W(-1)
VFD022EL43W(-1)
2.5 mm
2
[14 AWG]
VFD040EL43W(-1)
NOTE
For installation at an ambient temperature of 50°C, select copper wires with temperature resistance of 75°C or
90°C. For installation at an ambient temperature over 50°C, select copper wires with temperature resistance
of 90°C or above.
For installation of
VFD007EL21W(-1)
at an ambient temperature of 40°C, select copper wires with temperature
resistance of 75°C or 90°C. For installation at an ambient temperature over 40°C, select copper wires with
temperature resistance of 90°C or above.
When installing VFDxxxEL21W(-1), select wires with voltage rating of 300V
AC
or above. When installing
VFD
xxx
EL43W(-1), select wires with voltage rating of 600V
AC
or above.
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...