Chapter 1 Introduction
VFD-EL-W
1-7
1.2 Preparation for Installation and Wiring
1.2.1 Ambient Conditions
Install the AC motor drive in an environment with the following conditions.
Operation
Temperature
-10°C to 50°C (VFD007EL21W & VFD007EL21W-1,
fan required). After you install an optional cooling fan,
you can increase the operating temperature of these
two models up to 50°C without derating.
Relative Humidity
< 90%, non-condensing
Atmospheric pressure
86–106 kPa
Installation Site Altitude
<1000 m
Vibration
1.0 mm, peak-to-peak value: from 2–13.2 Hz;
0.7–1.0 G, from 13.2–55 Hz; 1.0 G, from 55–512 Hz;
compliance with IEC 60068-2-6 standard.
Storage
and
Transportation
Temperature
-20
°C
to 60°C (-4°F to 140°F)
Relative Humidity
< 90%, non-condensing
Atmospheric pressure
86–106 kPa
Vibration
1.0 mm, peak-to-peak value: from 2–13.2 Hz;
0.7–1.0 G, from 13.2–55 Hz; 1.0 G, from 55–512 Hz;
compliance with IEC 60068-2-6 standard.
Pollution Degree
2: good for a factory type environment.
Summary of Contents for VFD-EL-W Series
Page 7: ...v This page intentionally left blank ...
Page 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Page 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Page 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Page 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Page 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Page 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Page 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Page 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Page 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Page 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Page 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Page 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Page 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Page 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...