RTU-CN01 Operation Manual
5-12
5
Setting the input mode for a special module in the custom work mode
With a double-click on “04AD” symbol, the following special module configuration window appears right away.
Select “Custom” in the Work Mode field. For Link1 of output data, choose “CR1 -Input mode setting” with the
number set to 1. Then click “OK” to finish the setting.
Note:
1. CR1 in DVP04AD-S sets the work modes of four channels of the module. (Four modes per channel)
2. Based on the actual need, users use twelve bits of CR1 in the special module (bit 0 ~ bit 11) to set the
work mode for each channel individually.
3. For instance, to set the input mode to mode 0 (bit 2 ~ bit 0=000) for channel 1, to mode 1 (bit 5 ~ bit
3=001) for channel 2, to mode 2 (bit 8 ~ bit 6=010) for channel 3 and to mode 3 (bit 11 ~ bit 9=011) for
channel 4, the corresponding PDO value of CR1 should be set to 16#688.
4. The factory setting value of CR1 in DVP04AD-S is 0.
5. Refer to
DVP-PLC Application Manual: Special Modules
for more on DVP04AD-S.
Using Auto SDO to set the input modes for a special module
Click “Add SDO” button on the “Auto SDO” tab page. Choose the index 16#2000 since DVP04AD-S is the first
module on the right of RTU-CN01. Choose the subindex16#2 since CR1 is the parameter for input mode
setting.
To set the input mode to mode 3 for channel 1 and the input modes to mode 0 for channel 2~ channel 4, fill
16#3 in the “Data” field. Click “Add” to finish the setting.
Summary of Contents for RTU-CN01
Page 11: ...RTU CN01 Operation Manual 2 6 _2 MEMO...
Page 43: ...RTU CN01 Operation Manual 5 22 5 MEMO...
Page 53: ...RTU CN01 Operation Manual 6 10 _6 MEMO...
Page 68: ...Chapter 7 Application Examples 7 15 7_ Note Baud rate conversion 1 Mbps 1000 Kbps 1000000bps...
Page 75: ...RTU CN01 Operation Manual 7 22 _7 The complete configuration of Send PDO mappings is as below...