RTU-CN01 Operation Manual
6-2
_6
6.1
Parameters from EDS File
Parameters for digital modules on the right side of RTU-CN01
16#6000 and 16#6200 are parameters for digital modules on the right side of RTU-CN01. The index 16#6000
is the index for configuring input points. It contains 16 subindexes. Each subindex is configured with 8 input
points. Subindex 1 corresponds to the 1
st
8 point input of digital modules on the right side of RTU-CN01,
subindex 2 corresponds to the 2
nd
8 point input of digital modules on the right side of RTU-CN01 and so on.
Subindex 16 corresponds to the 16
th
8 point input of digital modules on the right side of RTU-CN01. Up to 128
input points can be configured in total.
The index 16#6200 is the index for configuring output points. It contains 16 subindexes. Each subindex is
configured with 8 output points. Subindex 1 corresponds to the 1
st
8 point output of digital modules on the
risght side of RTU-CN01, subindex 2 corresponds to the 2
nd
8 point output of digital modules on the right side
of RTU-CN01 and so on. Subindex 16 corresponds to the 16
th
8 point output of digital modules on the right
side of RTU-CN01. Up to 128 output points can be configured in total.
For example, there is one DVP16SN11T and one DVP16SM11T on the right side of RTU-CN01. And there
are 16 output points and 16 input points in total. Each subindex for input or output configuration can be
configured with 8 points and thus 2 subindexes are needed for the configuration of input points. That is, the
index 16#6000 and subindex 16#1 correspond to X0~X7 of DVP16SM11T and index 16#6000 and subindex
16#2 correspond to X10~X17 of DVP16SM11T. To configure the output points, the index 16#6200 and
subindex 16#1, which correspond to Y0~Y7 of DVP16SN11T and the index 16#6200 and subindex 16#2,
which correspond to Y10~Y17 of DVP16SN11T are used in the same way.
Parameters for special modules on the right side of RTU-CN01
The following 16#2000~16#20e0 are parameters for the special modules on the right of RTU-CN01. The
index 16#2000 is the index of the 1
st
special module on the right of RTU-CN01, 16#2020 is the index of the 2
nd
special module on the right of RTU-CN01 and so on. So in the same way,16#20e0 is the index of the 8
th
analog module on the right of RTU-CN01.
Summary of Contents for RTU-CN01
Page 11: ...RTU CN01 Operation Manual 2 6 _2 MEMO...
Page 43: ...RTU CN01 Operation Manual 5 22 5 MEMO...
Page 53: ...RTU CN01 Operation Manual 6 10 _6 MEMO...
Page 68: ...Chapter 7 Application Examples 7 15 7_ Note Baud rate conversion 1 Mbps 1000 Kbps 1000000bps...
Page 75: ...RTU CN01 Operation Manual 7 22 _7 The complete configuration of Send PDO mappings is as below...