97
Installation and Operating Manual for RPI M15A M20A Solar Inverter V1.0 2016-03-18
9 Settings
9.13 Reconnection time
This setting should only be changed after consul-
tation with Delta customer service.
Overview
Using this function you can set a reconnection time for occasions
when the inverter disconnects from the grid as a result of a volt-
age error or a frequency error.
After the error has disappeared, the inverter waits for the preset
reconnection time before connecting to the grid again.
Path to the menu item
Main Menu
>
Settings
>
Install Settings
>
Reconnection
Time
Setting options
Parameter
Description / Setting range
Reconnection
Time
Reconnection time in seconds
Setting the reconnection time
1.
If the default information is displayed, press the
EX IT
button
to open the main menu.
Alternatively, press the
EX IT
button repeatedly until the main
menu is displayed.
20
15
10
5
0
4
8
12
16
20
24
kW
2013.06.21
kWh
kWh
kg
2013.06.21
Hour
Peak Hours:
E-Day:
Day CO2 Saved:
Exit
Year
21. Jun 2013 09:30
Energy Log - Day
2.
Using the
and
buttons, select the
Settings
entry
and press the
ENT
button.
E-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3.
Using the
and
buttons, select the
Install Set-
tings
entry and press the
ENT
button.
Personal Settings
Coefficients Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings
4.
The function is protected with the password 5555.
Use the
and
buttons to set the individual digits.
Press the
ENT
button to confirm a digit.
3
3
3
3
ENT
21. Jun 2013 09:30
Password