77
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
Displayed information
Description
How can I change this setting
Dry Cont.B: Disabled
Dry Cont.A: Disabled
Max. Power: 55000W
AC connection: 3P4W
AC connection: 3P4W
The grid type (with or without a neutral con-
ductor).
See “8.4.9 AC connection”, page 102 for a
detailed description and how to change the
settings
Max. power: 55000W
The maximum active power limit of the
inverter.
See “8.4.10 Anti-islanding”, page 103 for a
detailed description and how to change the
settings
Dry Cont. A: Disable
Dry Cont. B: Disable
The event during which the relays trigger the
dry contacts.
See “5.9 Connecting an external alarm unit”,
page 39 for a detailed description and see
“8.4.6 Dry contacts”, page 98 for how to
change the settings
React Pwr Settings
Active Pwr Settings
Grid Settings
EPO: Normal close
EPO: Normal Open
The setting for the external power off relay.
Grid Settings
Sub-item with the settings for grid voltage, grid
frequency and reconnection time after a grid
error.
See “8.4.3 Country”, page 86 for a detailed
description and how to change the settings
Active Pwr Settings
Sub-item with the settings for the functions
controlling active power.
See below for a description.
React Pwr Settings
Sub-item with the settings for the functions
controlling reactive power.
See below for a description.
FRT Settings
FRT Settings
Function for setting the operating behavior in
the case of a grid voltage fail.
See “8.6 FRT (Fault Ride Through)”,
page 122 for a detailed description and how
to change the settings
Sub-item "Active Pwr Settings"
P(V)
Power vs. Frequency
Power Limit
Power limit
Function for power limiting
See “8.5.1 Power limit”, page 106 for a
detailed description and how to change the
settings
Power vs. Frequency
Function for regulating the active power
depending on the grid frequency.
See “8.5.2 Regulating the active power via
the grid frequency”, page 108 for a detailed
description and how to change the settings
P(V)
Function for regulating the active power
depending on the grid voltage.
See “8.5.3 P (V) (regulating the active power
via the grid voltage)”, page 111 for a detailed
description and how to change the settings
Sub-item "React Pwr Settings"
Q(V)
Constant Q
Cosphi (P)
Constant cosphi
Constant cos phi
Function for setting a constant cos phi (power
factor).
See “8.5.3 P (V) (regulating the active power
via the grid voltage)”, page 111 for a detailed
description and how to change the settings
Cos phi (P)
Function for regulating the cos phi (power fac-
tor) depending on the active power.
See “8.5.5 Cos phi (P) (regulate cos phi via
active power)”, page 115 for a detailed
description and how to change the settings
Constant Q
Function for setting a constant reactive power
See “8.5.6 Constant Q (constant reactive
power)”, page 117 for a detailed description
and how to change the settings
Q(V)
Function for regulating the reactive power
depending on the grid voltage.
See “8.5.7 Q (V) – Regulating reactive power
via voltage”, page 119 for a detailed descrip-
tion and how to change the settings