8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
108
8.5.2 Regulating the active power via the grid
frequency
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to regulate the active power fed into the
grid via the grid frequency.
Standard behavior of low-voltage power grids in Germany
(VDE-AR-N 4105)
Standard behavior of medium-voltage power grids in Ger-
many (BDEW)
Pm
f (Hz)
frestart = f
start
f
stop
Gradient (%/Hz)
Pm
f (Hz)
f
restart
f
stop
Gradient (%/Hz)
f
start
When the grid frequency exceeds f
start
the instantaneous value
of the active power is stored and the fed active power is reduced
according to the gradient.
The active power is regulated according to the gradient as long as
the grid frequency lies between f
start
and f
stop
.
The active power feed is stopped when the grid frequency
exceeds f
stop
.
feeding remains stopped until the grid frequency falls below f
start
again.
Feeding is resumed at the stored instantaneous value when the
grid frequency falls below f
start
again.
When the grid frequency exceeds f
start
the instantaneous value
of the active power is stored and the fed active power is reduced
according to the gradient.
The subsequent grid feed behavior depends on changes in the
grid frequency.
a)
When the grid frequency falls again, the fed active power stored
at this time is maintained before reaching f
stop
.
Feeding is resumed at the stored instantaneous value when the
grid frequency falls below f
restart
.
b)
The active power feed is stopped when the grid frequency
exceeds f
stop
.
Feeding remains stopped until the grid frequency falls below f
re-
start
.
Feeding is resumes at the stored instantaneous value when the
grid frequency falls below f
restart
again.
f
stop
is automatically calculated using the following formula:
f
stop
= f
start
+ (1 / gradient)