8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
86
8.4.3 Country
Change this setting only after consultation with
Delta customer service.
Overview
To change this setting, you need a special
password provided by Delta customer service.
You can find the contact information on the back
of this document.
This function allows you to set the country.
Setting options
Parameter
Description
Setting range
Country
Reset the inverter to the factory settings.
None
Menu item path
Main Menu > Install Settings > Country
Loading the factory settings
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
Enter the password provided by Delta customer service.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Grid Settings
Country
Insulation
Inverter ID: 001
4.
Use the
and
buttons to select the
Country
entry and then press the
ENT
button.
FRA-Is 60HZ
UK G59-3 230
FRA-Is 50HZ
FRA-Is 60HZ
FRANCE MV
5.
Use the
and
buttons to select your country or grid type and then press the
ENT
button.