8 Settings
8.5.5 Cos phi (P) (regulate cos phi via active
power)
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to regulate cos phi (cos φ) via the via
active power.
0.8
0.8
1.0
100%
P/P
n
cos φ
Upper
limit
Lower
limit
Lower
limit
Upper
limit
Setting options
Parameter
Description
Setting range
Mode
Switch the function on and off.
ON
|
OFF
Q upper
The upper limit of
cos phi (cos φ).
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
P lower
The lower limit of the active power.
0 .. 100%
Q lower
The lower limit of
cos phi (cos φ).
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
P upper
The upper limit of the active power.
0 .. 100%
V lock-in
230.0 .. 253.0 V
V lock-out
207.0 .. 230.0 V
Menu item path
Main Menu
>
Active/Reactive Pwr
>
Reactive Power Ctrl
>
Cos phi (P)
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.