8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
106
8.5 "Active/reactive power" menu area
This menu area is password-protected because
the settings in this menu area affect the energy
production of the inverter.
► Exercise extra care with all settings in this
menu area.
8.5.1 Power limit
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to additionally limit the active power. The
active power is specified as a percentage of the value set in the
Max. power
parameter (see “8.4.10 Anti-islanding”, page 103.
Example
Maximum power = 45,000 W
Power limit = 90%
Maximum active power = max. power x power limit
Maximum active power = 45,000 W x 90% = 40,500 W
Setting options
Parameter
Description
Setting range
Mode
Switch the function on and off.
ON
|
OFF
Define point
Additional active power limitation
0 .. 100%
Menu item path
Main Menu
>
Active/Reactive Pwr
>
Active Power Ctrl
>
Power Limit
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Active/Reactive Pwr
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.