7
•
Before applying electric power to the SVG, you must allow the SVG to adjust to room
temperature (20°C ~ 25°C (68°F ~ 77°F)) for at least one hour and ensure that there
is no moisture condensing inside the unit.
•
Do not put beverages on the SVG or any other accessory associated with the SVG.
•
Do not open or remove the covers or panels of the SVG to avoid high-voltage electric
shock. Only authorized Delta engineers or service personnel can do so for installation
or maintenance. If you want to open or remove the covers or panels, do it only under
the supervision of authorized Delta engineers or service personnel.
•
Some components like fans will become worn-out due to long-term usage, and this will
increase the risk of SVG failure. To replace and maintain the components, please
contact Delta service personnel.
•
The SVG complies with the regulations of Overvoltage Category III in IEC 62477. It
is suggested that appropriate surge voltage protection devices shall be chosen in
accordance with the actual power system type. If appropriate protection devices are
not used, the surge voltage may exceed the SVG's capacity and cause SVG
damage. If you are uncertain regarding the SVG's application, please contact Delta
service personnel.
Wiring
System
Recommended
Model
Main Technology Indicator
3P3W
Sichuan Zhongguang
Lightning
ZGG40-385
(3+0)
Ar
Nominal Operating Voltage U
o
:
230V AC
Max. Continuous Operating Voltage U
c
:
385V AC
Rated Discharge Current I
n
:
20
kA
Max. Discharge Current I
max
:
40
kA
Voltage Protection Level U
p
:
1.8
kV
3P4W
Sichuan Zhongguang
Lightning
ZGG40-385
(3+1)
r
•
You must contact Delta customer service if any of the following events occurs:
1. Any liquid is poured or splashed on the SVG.
2. The SVG is deformed.
3. Any conductive powders or metals enter into the SVG.
4. The SVG does not run normally after you carefully followed the instructions in this
User Manual
.