PQC Series
Static Var Generator
42
(Figure 3-22: Multiple Module Parallel System_ Wiring between the Display,
SVG Module and CT)
WARNING:
The display communication cables are secondary wires and shall be kept an
insulation distance of no less tha
n 100mm from
the main power cables.
7. SVG module’s supporting structure and installation procedures:
1)
Fix the module and the installation panel together as shown in
Figure 3-23
.
2)
Fix the installation panel with the supporting beams on the left and right of the
cabinet as shown in
Figure 3-24
.