19
NOTE:
1. Except for the dry contacts and wet contacts, other terminals are insulated.
Contacting these terminals will not cause the risk of electric shock.
2. Specifications of the dry contacts and wet contacts are as follows.
No.
Item
Description
❶
OUTPUT (Dry Contacts)
250Vac/ 30Vdc
,
2.5A
❷
INPUT (Wet Contacts)
24V
,
10mA
For the definition of Output Dry Contact Signals interface, please refer to
Table 2-6
.
Table 2-6: The Definition of Output Dry Contact Signals Interface
Item
Pin No
Signal
Electrical Character
Function
OUTPUT
(Dry Contacts)
1
RUN-A
250 Vac/ 30 Vdc
2.5A
Run state (PM
Run, Close)
2
RUN-B
250 Vac/ 30 Vdc
2.5A
3
FAULT-A
250 Vac/ 30 Vdc
2.5A
Fault state (PM
Fault, Close)
4
FAULT-B
250 Vac/ 30 Vdc
2.5A
5
FAN-A
250 Vac/ 30 Vdc
2.5A
Fan control (Fan
ON, Close; Fan
OFF, Open)
6
FAN-B
250 Vac/ 30 Vdc
2.5A
For the definition of Input Wet Contact Signals interface, please refer to
Table 2-7
.
Table 2-7: The Definition of Input Wet Contact Signals Interface
Item
Pin No
Signal
Electrical Character
Function
INPUT
(Wet Contacts)
1
EPO-2
24V
10 mA
System EPO
(Close, Enable Open,
Disable )
2
EPO-1 24V 10
mA
3
SPD-A 24V 10
mA
System SPD
(Close, SPD Fault
Open, NO Fault)
4
SPD-B 24V 10
mA