31
SVG Rated
Capacity
(kvar)
Breaker
Size (A)
R/S/T Wire
Diameter
N Wire
Diameter
(3P4W)
N Wire
Diameter
(3P3W)
PE Wire
Diameter
350 kvar
700A
2
×
150 mm
2
2
×
150 mm
2
1.5
mm
2
150
mm
2
400 kvar
800A
2
×
185 mm
2
2
×
185 mm
2
1.5 mm
2
185
mm
2
500 kvar
400A+630A
or 1000A
2
×
240 mm
2
2
×
240 mm
2
1.5 mm
2
240
mm
2
600 kvar
630A+630A
or 1250A
2
×
300 mm
2
2
×
300 mm
2
1.5 mm
2
240
mm
2
700 kvar
630A+800A
or 1400A
2
×
400 mm
2
2
×
400 mm
2
1.5
mm
2
240
mm
2
NOTE:
1. Temperature endurance of above wires shall be 70°C (158°F).
2. If the Neutral line current of SVG is bigger than phase line current, the Neutral
line needs bigger diameter, please contact Delta service personnel.
3. For 3P3W model, configure 1.5 mm
2
wire on cabinet Neutral terminal is used
to supply phase voltage to cabinet AC fans.
4. If the SVG only outputs reactive current, the breaker size shown in
Table 3-1
should be multiplied by 0.8 ~ 0.9.
6.
Connect the power wires from SVG cabinet power cable terminals to external
breaker or feeder, and finally, to the power supply system.