Delta Electronics. Inc.
HPH-
20KA01KAT
29
Note 6.2: Check Sum value is the summation of “1” signal calculated by byte 0 to 7.
Example:
“Master IP is 01, Power On”, Byte 0~7 are “0x01-0x41-0x00-0x00-0x00-0x00-0x00-0x00”.
There are three “1” in this command, so checksum is 3.
Note 6.3: Use 9600bps, 8 data bits, no parity, 1 stop bit (9600/8-N-1).
Note 6.4: PSU state Byte 4(Warning) and Byte 5(Alarm) value refer to table 4.1
Table 6.5 Value definition (Translate decimal to hexadecimal for utilizing)
Command
Byte3
Byte4
Byte5
Byte6
CV Mode
0 to 1000 for 0 to 1000V
CC Mode
0 to 500 for 0~50.0A
CP Mode
0 to 200 for 0 to 20.0kW
Master/Slave
Master: 00, Slave: 01
A/Ri Offset
Plus: 00, M
inus: 01
0 to 99 for 0 to 9.9%
A/Vo Offset
Plus: 00, M
inus: 01
0 to 99 for 0 to 9.9%
A/Io Offset
Plus: 00, M
inus: 01
0 to 99 for 0 to 9.9%
Terminating Resistor
IP for
1
to 16
OFF: 0, On: 1
Set Point
1 to 10 for 1 to 10s
Pause Time
4 to 25 for 40 to 250us, Scale: 10us
Energy Mode
1 to 99999 for 1 to 99999kJ, 0: OFF
Arc Function
OFF: 0, ON: 1
Parallel Number
1 to 16 for 1 to 16 sets
Max Power
20 to 200 for 2 to 20kW
Max Current
50 to 500 for 5 to 50A
Max Voltage
500 to 1000 for 500 to 1000V
Ramp Time
5 to 200 for 50 to 2000ms
Target Life
0 to 1500000 for OFF to 15000.00kWh, 0: OFF
Delay time
0 to 5 for 0 to 5us
Arc Voltage
25 to 200 for 25 to 200V
Arc Density
0 to 99 for 0 to 99 times/s
Arc Number
0 to 999 for 0 to 999 times
Ignition
10 to 19 for 1000 to 1900V
Summary of Contents for HPH-20KA01KAT
Page 1: ...User Manual DC Power Supply Continuous 400 1000 VDC Model HPH 20KA01KAT Version Rev S 00...
Page 13: ...Delta Electronics Inc HPH 20KA01KAT 9...
Page 15: ...Delta Electronics Inc HPH 20KA01KAT 11...
Page 22: ...Delta Electronics Inc HPH 20KA01KAT 18...
Page 29: ...Delta Electronics Inc HPH 20KA01KAT 25 6 3 Main Menu Map Fig 6 1 Panel tree...