Delta Electronics. Inc.
HPH-
20KA01KAT
35
Bus OVP
21
Input voltage is over operation range
Take all safety precaution, and
then check if the mains voltage
that is in specification.
GND Detect
22
Positive output is not connected to
protective earth
Check if the output positive
terminal is short to protective
earth.
Set Point Monitor
23
Error while output fails to reach
setting parameter within setting time
Take all safety precaution, and
then turn on the output power
with a dummy load to ensure if
it is under normal operation.
Energy Mode Monitor
24
Power off while output reaches
setting Energy
Monitor Setting is end. Press
and hold “OFF” button with 10
second to clear error.
Parallel Fault IP1
101 Fault from PSU IP 01
Check the PSU with IP 01
independently to ensure the
operation is normal.
Parallel Fault IP2
102 Fault from PSU IP 02
Check the PSU with IP 02
independently to ensure the
operation is normal.
Parallel Fault IP3
103 Fault from PSU IP 03
Check the PSU with IP 03
independently to ensure the
operation is normal.
Parallel Fault IP4
104 Fault from PSU IP 04
Check the PSU with IP 04
independently to ensure the
operation is normal.
Parallel Fault IP5
105 Fault from PSU IP 05
Check the PSU with IP 05
independently to ensure the
operation is normal.
Parallel Fault IP6
106 Fault from PSU IP 06
Check the PSU with IP 06
independently to ensure the
operation is normal.
Parallel Fault IP7
107 Fault from PSU IP 07
Check the PSU with IP 07
independently to ensure the
operation is normal.
Parallel Fault IP8
108 Fault from PSU IP 08
Check the PSU with IP 08
independently to ensure the
operation is normal.
Parallel Fault IP9
109 Fault from PSU IP 09
Check the PSU with IP 09
independently to ensure the
operation is normal.
Parallel Fault IP10
110
Fault from PSU IP 10
Check the PSU with IP 10
independently to ensure the
operation is normal.
Parallel Fault IP11
111
Fault from PSU IP 11
Check the PSU with IP 11
independently to ensure the
operation is normal.
Parallel Fault IP12
112
Fault from PSU IP 12
Check the PSU with IP 12
independently to ensure the
operation is normal.
Parallel Fault IP13
113
Fault from PSU IP 13
Check the PSU with IP 13
independently to ensure the
operation is normal.
Summary of Contents for HPH-20KA01KAT
Page 1: ...User Manual DC Power Supply Continuous 400 1000 VDC Model HPH 20KA01KAT Version Rev S 00...
Page 13: ...Delta Electronics Inc HPH 20KA01KAT 9...
Page 15: ...Delta Electronics Inc HPH 20KA01KAT 11...
Page 22: ...Delta Electronics Inc HPH 20KA01KAT 18...
Page 29: ...Delta Electronics Inc HPH 20KA01KAT 25 6 3 Main Menu Map Fig 6 1 Panel tree...