3 - 11
3 Operation Modes
3.10 Common Battery
To save on your costs and installation space, parallel UPSs can share external battery cabi-
nets. In common battery mode, please install an isolated switch between each UPS and its
connected battery cabinets. Please see
Figure 3-10
for two parallel UPSs sharing one ex-
ternal battery cabinet.
(Figure 3-10: Path of Electrical Power through the Parallel UPSs in Common Battery Mode)
UPS 1
LOAD
UPS 2
BYPA.
MAIN
BYPA.
MAIN
Circuit
Breaker
Batteries
Q3 Switch
Q2 Switch
Q1 Switch
Rectifier
Inverter
STS
Q4 Switch
Q3 Switch
Q2 Switch
Q1 Switch
Rectifier
Inverter
STS
Q4 Switch
If parallel UPSs share external battery cabinets, you should use the control panel to set up
‘TYPE(AH)’, ‘BAT STRINGS’, ‘FLOAT CHARGE VOLT(V)’, ‘BOOST CHARGE VOLT(V)’,
and ‘CHARGE CURRENT(A)’. Please refer to
8.7.3 Battery Setup
and
8.7.4 Charger
Setup
.
NOTE:
3OHDVHQRWHWKDW\RXVKRXOGVHWHDFK836ÀRDWYROWDJHGHIDXOW9WKHVDPH
each UPS boost voltage (default: 288V) the same, and set each UPS charge
current even. For example, when two UPSs are paralleled, they share one battery
cabinet, battery type is 120AH, and you want to set the battery cabinet’s charge
current as 20A. You should set each UPS ‘TYPE(AH)’ as 60AH, ‘BAT STRINGS’ as
1, and ‘CHARGE CURRENT(A)’ as 10A.
Summary of Contents for DPS-500K
Page 38: ...3 12 Ultron DPS Series...
Page 46: ...4 8 Ultron DPS Series...
Page 80: ...6 12 Ultron DPS Series...
Page 110: ...7 30 Ultron DPS Series...
Page 132: ...8 22 Ultron DPS Series...
Page 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Page 135: ...10 1 10 Maintenance Maintenance 10...
Page 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Page 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 148: ...A1 4 Ultron DPS Series...
Page 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 151: ......
Page 152: ...5013238900...