8 - 1 3
8 LCD Display & Settings
y
FLOAT CHARGE VOLT (V)
6HWXSÀRDWFKDUJHYROWDJH
y
BOOST CHARGE VOLT (V)
Set up boost charge voltage.
y
CHARGE CURRENT (A)
Set up charge current.
y
AUTO BOOST CHARGE
Set up ‘AUTO BOOST CHARGE’ as ON or OFF.
y
AUTO BOOST CHARGE PERIOD (MONTH)
Set up auto boost charge period (month).
y
AUTO BOOST CHARGE TIME (HOUR)
Set up auto boost charge time (hour).
8.7.5 Parallel Setup
5RXWH0DLQ6FUHHQĺ0DLQ0HQXĺ8366HWXS &RQWUROĺ3DUDOOHO6HWXS
If you parallel UPSs, please go to
PARALLEL SETUP
screen shown below to set up a
parallel group ID No. and a parallel ID No. for each parallel UPS.
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
PARALLEL SETUP
PARALLEL GROUP
PARALLEL ID
1
1
y
PARALLEL GROUP
Set up a parallel group ID No. (1~2) for each parallel UPS.
If all parallel UPSs connect to the same group of critical loads, set each parallel UPS’s
parallel group ID No. as 1.
If parallel UPSs connect to different groups of critical loads (maximum group: two), set
each UPS’s parallel group ID No. as 1 or 2 accordingly.
Summary of Contents for DPS-500K
Page 38: ...3 12 Ultron DPS Series...
Page 46: ...4 8 Ultron DPS Series...
Page 80: ...6 12 Ultron DPS Series...
Page 110: ...7 30 Ultron DPS Series...
Page 132: ...8 22 Ultron DPS Series...
Page 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Page 135: ...10 1 10 Maintenance Maintenance 10...
Page 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Page 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 148: ...A1 4 Ultron DPS Series...
Page 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 151: ......
Page 152: ...5013238900...