3 - 9
3 Operation Modes
3.8 Bypass Mode (Parallel)
UPS 1
LOAD
UPS 2
MAIN
BYPA.
BYPA.
MAIN
Q3 Switch
Q2 Switch
Q1 Switch
Rectifier
Inverter
Circuit
Breaker
Batteries
STS
Q4 Switch
Q3 Switch
Q2 Switch
Q1 Switch
Rectifier
Inverter
Circuit
Breaker
Batteries
STS
Q4 Switch
(Figure 3-8: Path of Electrical Power through the Parallel UPSs in Bypass Mode)
In parallel mode, when all inverters encounter abnormal situations such as over
temperature, overload, short circuit, abnormal output voltage and battery depletion, they will
automatically shut themselves down to protect the UPSs’ systems. Meanwhile, if all UPSs
detect the bypass AC source is normal, they will automatically switch to bypass mode to
protect the connected critical loads from power interruption. The critical loads will be equally
shared by all parallel units. After the abnormalities mentioned above are eliminated, the
UPSs will switch back to normal mode from bypass mode. During bypass mode, all parallel
UPSs’ LEDs illuminate as follows.
Fault
Summary of Contents for DPS-500K
Page 38: ...3 12 Ultron DPS Series...
Page 46: ...4 8 Ultron DPS Series...
Page 80: ...6 12 Ultron DPS Series...
Page 110: ...7 30 Ultron DPS Series...
Page 132: ...8 22 Ultron DPS Series...
Page 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Page 135: ...10 1 10 Maintenance Maintenance 10...
Page 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Page 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 148: ...A1 4 Ultron DPS Series...
Page 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 151: ......
Page 152: ...5013238900...