7 - 1 0
Ultron DPS Series
8
During normal mode, LEDs illuminate as follows.
Fault
7.1.5 Normal Mode Turn-off Procedures (Single)
1
During normal mode, the following screen appears and LEDs illuminate as follows.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD PROTECTED
ON LINE
Fault
2
Press
the
OFF
button
on the control panel for three to ten seconds and release it
after you hear one beep. The LCD shows the message:
‘SHUTDOWN UPS?’
. Select
‘YES’
and press the function key below the symbol ‘
¶WRFRQ¿UP\RXUVHOHFWLRQ
3
After you confirm your selection, the UPS transfers from normal mode into bypass
mode, the following screen appears and LEDs illuminate as follows.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
Fault