7 - 1 5
7 UPS Operation
7.2.1 Normal Mode Start-up Procedures (Parallel)
1
Turn on the circuit breakers or fuses of all external battery cabinets.
2
Switch on each UPS's Bypass Switch (Q2). After initialization, all fans start running,
each unit's Bypass AC Source LED
and Bypass Power Supply LED
illuminate,
and the following screen appears on each unit's LCD.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
TO BROWSE EVENT
(004)
PRESS
3
Turn on each UPS’s Input Switch (Q1), each unit’s Main AC Source LED
illuminates, each UPS’s DC BUS voltage starts establishing, and the following screen
appears on each unit’s LCD.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
TO BROWSE EVENT
(004)
PRESS
4
Press
each
UPS’s
ON
button
for three to ten seconds and release it after you hear
one beep. In the meantime, each unit’s inverter starts up, each unit’s Inverter Start-up
LED
is on, each UPS is in bypass mode, and the following screen appears on each
unit’s LCD.
Summary of Contents for DPS-500K
Page 38: ...3 12 Ultron DPS Series...
Page 46: ...4 8 Ultron DPS Series...
Page 80: ...6 12 Ultron DPS Series...
Page 110: ...7 30 Ultron DPS Series...
Page 132: ...8 22 Ultron DPS Series...
Page 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Page 135: ...10 1 10 Maintenance Maintenance 10...
Page 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Page 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 148: ...A1 4 Ultron DPS Series...
Page 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 151: ......
Page 152: ...5013238900...