6. Fire Detection: Select
☑
; an alarm will
be generated when the fire and
smoke dry contact status transitions.
Actuator Alarm
Main menu
→
Setting
→
Set Alarm
→
Actuator Alarm
, press
key to
enter.
The driver alarm page can be adjusted
by the user, as explained below
1. Ball Valve: Select
☑
; an alarm will be
generated when the ball valve is
abnormal.
2. Fan 1~5: Select
☑
; an alarm will be
generated when the fan is abnormal.
Out of Range
Main menu
→
Setting
→
Set Alarm
→
Out of Range
, press
key to
enter.
The out-of-range alarm page can be
adjusted by the user, as explained below
1. Supply Air T High: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the outlet air
temperature is higher than the
configured value, an alarm will be
generated.
2. Supply Air T Low: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the outlet air
temperature is lower than the
configured value, an alarm will be
generated.
3. Return Air T High: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the outlet air
temperature is higher than the
configured value, an alarm will be
generated.
4. Remote Air T High: It can be turned
on by
☑
; an appropriate temperature
Ball Valve :☑
Fan 1 :☑
Fan 2 :☑
Fan 3 :☑
Fan 4 :☑
Fan 5 :
󠆭