71
Event
ID
Alarm Name
Alert
Level
*
System Action
after Alarm
Possible Cause
Method of
Exclusion
106
Remote T Low
1
Alarm display
1. The air setting
is abnormal
2. The configured
value of the
alarm is
incorrect
1. Confirm whether
the temperature
setting for each
outlet is correct
2. Check the
configured value
of the alarm
114
Remote DP T
High
1
Alarm display
1. Environmental
humidity is too
high
2. The configured
value of the
alarm is
incorrect
1. Check the
environmental
humidity or add
a dehumidifier
2. Check the
configured value
of the alarm
148
Over
Maintenance
Time
1
Alarm display
1. Over
maintenance
time
1. Perform
maintenance
166
Water Inlet T
High
1
Alarm display
1. Abnormal
temperature of
chilled water
supply
2. Chilled water
supply flow is
too low
3. The configured
value of the
alarm is
incorrect
1. Check whether
the temperature
of the chilled
water circuit is
too high
2. Check whether
the working
condition of the
chilled water
circuit pump is
normal
3. Check the
configured value
of the alarm
168
Water Inlet T
Low
1
Alarm display
1. Abnormal
temperature of
chilled water
supply
2. The configured
value of the
alarm is
incorrect
1. Check whether
the temperature
of the chilled
water circuit is
too low
2. Check the
configured value
of the alarm