81
Model No.
Unit
RWC030D0AK00B8
RWC050D0AK00B8
Turbo Boost
Control
1. Fan failure
Increase the fan speed
of neighboring
machines.
2. Ball valve failure
Reduce the air outlet
temperature setting of
the adjacent machines.
3. Shared condensation
alarm
Rise the air outlet
temperature setting to
26
°
C
to reduce the
condensation.
1. Fan failure
Increase the fan speed
of neighboring machines.
2. Ball valve failure
Reduce the air outlet
temperature setting of
the adjacent machines.
3. Shared condensation
alarm
Rise the air outlet
temperature setting to 26
°
C
to reduce the
condensation.
Height
Inches
77.4" (for 42U rack)
77.4" (for 42U rack)
Width
Inches
23.6" (for 600mm rack)
23.6" (for 600mm rack)
Depth
Inches
13.6"
13.6"
Weight
lbs
198
216
Certification
CE
CE
Optional
1. Air pressure control
2. PICV valve
3. Inlet water cut-off valve
4. T/ RH sensor at cold
aisle
5. Flower meter
6. Quick disconnect
couplings
7.
Dual power feed/ ATS
1. Air pressure control
2. PICV valve
3. Inlet water cut-off valve
4. T/ RH sensor at cold
aisle
5. Flower meter
6. Quick disconnect
couplings
7.
Dual power feed/ ATS