InfraSuite - CoolDoor
36
4.2
Connect the Signal Cables
Connect the signal cables (upper incoming cable)
It is suggested that you use cables with wire diameter of 22 AWG or larger, and use a suitable
conduit or bushing for each cable protection.
Step 1
Use needle-nose pliers to remove the knockers at the top of the rack, and then take out the
cable protection ring from the accessory bag. Put the protection ring on the perforated hole,
as shown in
Figure 4-2
.
(Figure 4-2: Upper Incoming Signal Cable Position)
Step 2
Route the signal cable through the equipment to the signal cable inlet on the top of the rack.
Step 3
Push the signal cable into the hole of the signal cable inlet on the top of the rack and connect
it to the terminal block in the rack, as shown in
Figure 4-3
.
Step 4
Use the binding strap to fix the signal cable to the proper position in the device.