Chapter 6 Fault Code Information and Maintenance
|
Revision Nov. 2008, VLE1, SW V1.03 6-11
6.2 Maintenance and Inspections
Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10
minutes after all display lamps have gone out, and then confirm that the capacitors have fully
discharged by measuring the voltage between DC+ and DC-. The voltage between DC+ and DC-
should be less than 25VDC.
Ambient environment
Maintenance
Period
Check Items
Methods and Criterion
Daily
Half
Year
One
Year
Check the ambient temperature,
humidity, vibration and see if
there are any dust, gas, oil or
water drops
Visual inspection and measurement
with equipment with standard
specification
{
If there are any dangerous
objects
Visual inspection
{
Voltage
Maintenance
Period
Check Items
Methods and Criterion
Daily
Half
Year
One
Year
Check if the voltage of main
circuit and control circuit is
correct
Measure with multimeter with standard
specification
{
Keypad
Maintenance
Period
Check Items
Methods and Criterion
Daily
Half
Year
One
Year
Is the display clear for reading
Visual inspection
{
Any missing characters
Visual inspection
{
Summary of Contents for Elevator Drive VFD-VL
Page 1: ......
Page 2: ......
Page 3: ......
Page 21: ...Chapter 1 Introduction 1 12 Revision Nov 2008 VLE1 SW V1 03 20 30HP 15 22kW frame D...
Page 25: ...Chapter 1 Introduction 1 16 Revision Nov 2008 VLE1 SW V1 03 This page intentionally left blank...
Page 205: ...Appendix B Accessories B 8 Revision Nov 2008 VLE1 SW V1 03 VFDB4132 VFDB4132 CHARGE ACT OC OH...
Page 238: ...Appendix B Accessories Revision Nov 2008 VLE1 SW V1 03 B 41 Order P N 200TDDS84C...
Page 243: ...Appendix B Accessories B 46 Revision Nov 2008 VLE1 SW V1 03 This page intentionally left blank...