Chapter 4 Parameters
|
Revision Nov. 2008, VLE1, SW V1.03 4-65
06-10
Over-torque Detection Time (OT2)
Unit: 0.1
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0.1
Settings
0.0 to 60.0 sec
Pr.06-05 and Pr.06-08 determine the operation mode of the drive after the over-torque is
detected via the following method: if the output current exceeds the over-torque detection level
(Pr.06-06) and also exceeds the Pr.06-07 Over-Torque Detection Time, the fault code
“OT1/OT2” is displayed. If a Multi-Functional Output Terminal is to over-torque detection, the
output is on. Please refer to Pr.02-11~02-22 for details.
5%
Pr.06-06,
Pr.06-09
Pr.06-07, 06-10
current
06-11
Current Limit
Unit: 1
Control
mode
FOCPG
TQCPG
Factory setting: 150
Settings
0 to 250%
It is used to set the current limit.
06-12
Electronic Thermal Relay Selection
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 2
Settings
0
Inverter
motor
1
Standard
motor
2
Disabled
It is used to prevent self-cooled motor overheats under low speed. User can use electrical
thermal relay to limit driver’s output power.
06-13
Electronic Thermal Characteristic
Unit: 0.1
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 60.0
Settings
30.0 to 600.0 sec
Summary of Contents for Elevator Drive VFD-VL
Page 1: ......
Page 2: ......
Page 3: ......
Page 21: ...Chapter 1 Introduction 1 12 Revision Nov 2008 VLE1 SW V1 03 20 30HP 15 22kW frame D...
Page 25: ...Chapter 1 Introduction 1 16 Revision Nov 2008 VLE1 SW V1 03 This page intentionally left blank...
Page 205: ...Appendix B Accessories B 8 Revision Nov 2008 VLE1 SW V1 03 VFDB4132 VFDB4132 CHARGE ACT OC OH...
Page 238: ...Appendix B Accessories Revision Nov 2008 VLE1 SW V1 03 B 41 Order P N 200TDDS84C...
Page 243: ...Appendix B Accessories B 46 Revision Nov 2008 VLE1 SW V1 03 This page intentionally left blank...