Particulate contamination
Specifications
NOTE:
This condition applies to data center and non-data center
environments.
Table 33. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Dell EMC PowerEdge R640 Installation and Service Manual
Technical specifications