CAUTION:
To ensure proper system cooling, the PSU blank must be installed in the second PSU bay in a non-redundant
configuration. Remove the PSU blank only if you are installing a second PSU.
Figure 80. Removing a power supply unit blank
Next step
Install a PSU, for more information, see
Installing a hot swappable power supply unit
or install a PSU blank, for more information, see
.
Installing a power supply unit blank
Prerequisites
1
Follow the safety guidelines listed in
2
Install the power supply unit (PSU) blank only in the second PSU bay.
Step
Align the PSU blank with the PSU slot and push it into the PSU slot until it clicks into place.
Figure 81. Installing a power supply unit blank
Removing a hot swappable power supply unit
Prerequisites
CAUTION:
The system needs one power supply unit (PSU) for normal operation. On power-redundant systems, remove and
replace only one PSU at a time in a system that is powered on.
1
Follow the safety guidelines listed in
2
Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable from the
strap on the PSU handle.
116
Installing and removing system components