l
Before touching any unit, touch a bare (unpainted) metal surface of the cabinet/rack or
enclosure.
l
Before removing any unit from its antistatic bag, place one hand firmly on a bare metal surface
of the cabinet/rack or enclosure, and at the same time, pick up the unit while it is still sealed in
the antistatic bag. At the same time, do not move around the room or touch other furnishings,
personnel, or surfaces until you have installed the unit.
l
When you remove a unit from the antistatic bag, avoid touching any electronic components
and circuits on it.
l
If you must move around the room or touch other surfaces before installing a unit, first place
the unit back in the antistatic bag. When you are ready again to install the unit, repeat these
procedures.
Hardware acclimation times
Units must acclimate to the operating environment before applying power. This requires the
unpackaged system or component to reside in the operating environment for up to 16 hours in
order to thermally stabilize and prevent condensation.
Transit/storage environment
Operating environment
temperature
Acclimation time
Temperature
Humidity
Nominal
68-72°F
(20-22°C)
Nominal
40-55% RH
Nominal 68-72°F (20-22°C)
40-55% RH
0-1 hour
Cold
<68°F (20°C)
Dry
<30% RH
<86°F (30°C)
4 hours
Cold
<68°F (20°C)
Damp
≥30% RH
<86°F (30°C)
4 hours
Hot
>72°F (22°C)
Dry
<30% RH
<86°F (30°C)
4 hours
Hot
>72°F (22°C)
Humid
30-45% RH
<86°F (30°C)
4 hours
Humid
45-60% RH
<86°F (30°C)
8 hours
Humid
≥60% RH
<86°F (30°C)
16 hours
Unknown
<86°F (30°C)
16 hours
l
If there are signs of condensation after the recommended acclimation time has passed, allow
an additional eight (8) hours to stabilize.
l
Systems and components must not experience changes in temperature and humidity that are
likely to cause condensation to form on or in that system or component. Do not exceed the
shipping and storage temperature gradient of 45°F/hr (25°C/hr).
FRU Removal and Replacement
Dell EMC FS25 SSD Shelf Guide Field Replacement Unit Guide
15
Summary of Contents for FS25
Page 1: ...Dell EMC FS25 SSD Shelf Guide Version 7 0 Field Replacement Unit Guide Rev 01 September 2019 ...
Page 6: ...Figures 6 Dell EMC FS25 SSD Shelf Guide Field Replacement Unit Guide ...
Page 8: ...Tables 8 Dell EMC FS25 SSD Shelf Guide Field Replacement Unit Guide ...
Page 12: ...Revision history 12 Dell EMC FS25 SSD Shelf Guide Field Replacement Unit Guide ...
Page 30: ...FRU Removal and Replacement 30 Dell EMC FS25 SSD Shelf Guide Field Replacement Unit Guide ...