Condition
Comment
MAINS FAILURE IN
###s
Frequency or voltage measurement is outside the lim-
its
The timer shown is
the Mains failure de-
lay.Text in mains units
MAINS U OK DEL ####s
Mains voltage is OK after a mains failure
The timer shown is
the Mains OK delay
MAINS f OK DEL ####s
Mains frequency is OK after a mains failure
The timer shown is
the Mains OK delay
Hz/V OK IN ###s
The voltage and frequency on the genset is OK
When the timer runs
out it is allowed to op-
erate the generator
breaker
COOLING DOWN ###s
Cooling-down period is activated
COOLING DOWN
Cooling-down period is activated and infinite
Cooling down timer is
set to 0.0 s
GENSET STOPPING
This info is shown when cooling down has finished
EXT. STOP TIME ###s
EXT. START ORDER
A planned AMF sequence is activated
There is no failure on
the mains during this
sequence
7.24 Counters
Counters for various values are included, and some of these can be adjusted if necessary, for instance if the
unit is installed on an existing genset or a new circuit breaker has been installed.
The table shows the adjustable values and their function in menu 6100:
Description
Function
Comment
6101 Running time
Offset adjustment of the total running hours
counter.
Counting when the running feedback
is present.
6102 Running time
Offset adjustment of the total running thou-
sand hours counter.
Counting when the running feedback
is present.
6103 GB opera-
tions
Offset adjustment of the number of genera-
tor breaker operations.
Counting at each GB close command.
6104 MB opera-
tions
Offset adjustment of the number of mains
breaker operations.
Counting at each MB close command.
6105 kWh reset
Resets the kWh counter.
Automatically resets to OFF after the
reset. The reset function cannot be left
active.
6106 Start at-
tempts
Offset adjustment of the number of start at-
tempts.
Counting at each start attempt.
CGC 400 DRH 4189340786 UK
Additional functions
DEIF A/S