The mains OK delay is not used at all when the "Mains Okay" input is configured.
Mains OK
Mains OK
delay
MB input
configured
Expired
MB control
input
ON
MB and GB
operation
Sequence
Yes
No
No
No
Yes
Yes
7.8 Command timers
The purpose of the command timers is to be able to e.g. start and stop the genset automatically at specific
times each weekday or certain weekdays. If auto mode is activated, this function is available in island opera-
tion and load takeover operation. Up to four command timers can be used for e.g. start and stop. The com-
mand timers are available in M-Logic and can be used for other purposes than starting and stopping the gen-
set automatically. The settings can either be set up through the PC utility software or the display. Each com-
mand timer can be set for the following time periods:
●
Individual days (MO, TU, WE, TH, FR, SA, SU)
●
MO, TU, WE, TH
●
MO, TU, WE, TH, FR
●
MO, TU, WE, TH, FR, SA, SU
●
SA, SU
To start in AUTO mode, the "Auto start/stop" command can be programmed in M-Logic or in
the input settings.
The time-dependent commands are flags that are raised when the command timer is in the ac-
tive period.
CGC 400 DRH 4189340786 UK