Multi-input 58 and 59 cannot be used for this purpose.
When the oil pressure increases above the adjusted value
(6175 Pressure level),
the running feedback is
detected, and the start sequence is ended.
Running feedback
t
RPM
RPM
NOM
Run detection
Oil pressure
menu 6175
RPM / Oil pressure
Firing speed
Remove starter input
The drawing below shows how the setpoint of the "remove starter input" is detected at the firing speed level.
The factory setting is 400 RPM
(6170 Running detect.).
t
RPM
RPM
NOM
Remove starter,
menu 6161
RPM / Oil pressure
Firing speed Running
Run detection
Oil pressure
menu 6175
The remove starter function can use the MPU or a digital input.
CGC 400 DRH 4189340786 UK
Additional functions
DEIF A/S
Page 48 of 96