7.20.9 Configuration
The eight curve settings for the configurable RMI inputs cannot be changed in the display, but
only
in the PC
utility software. In the PC utility software the configurable inputs are adjusted in this dialogue box:
Adjust the resistance of the RMI sensor at the specific measuring value. In the example above the adjustment
is 10 Ω at 0.0 bar.
7.20.10 Scaling of 4-20 mA inputs
The scaling of the analogue inputs is made to ensure that the readout of the inputs is made with a resolution
that fits the connected sensor. It is recommended to follow the guide below when changing the scaling of the
analogue inputs.
Scaling example:
1. Use the utility software to configure a multi-input to be 4-20 mA, in this example multi-input 6 (parameter
10980)
2. Read the parameters from the device
3. After reading the parameters, the 4-20 mA alarm appears under the analogue fane in the USW. The ex-
ample below shows how to adjust the analogue input alarm.
The three dots to the left of the figures, marked with arrows, are buttons. Adjust the input as required, e.g.
0-5 bar: