Evaluation table for...
Note
:
The module has to be removed for testing
(measuring)!
Note
:
The module has to be removed for testing
(measuring)!
DEHNrail modular
Protection modules
Type
Part No.
(
Pin 1
Þ
2)
DR MOD 255
953 010
635
966** 485 595
DR MOD 30
953 011
70
110** 48 60
DR MOD 60
953 012
182
279** 121 150
DR MOD 75
953 013
182
279** 146 181
DR MOD 150
953 014
277
424** 269 331
DR M MOD 4P 255
953 020
675
1006
386
474
(
Pin 1,2
Þ
PE)
(
Pin L1,L2,L3
Þ
N)
(
Pin N
Þ
PE)
busbar
BBA protection module
Type
Part No.
T 275 BBA
950 204
386
491
T C 255 BBA
950 205
397
604
VM surge protective
device
Type
Part No.
VM 280
900 400
386
474
VM 280 FM
900 420
386
474
Note
:
The SPD has to be removed for testing
(measuring)!
Note:
The protective device has to be removed for
testing (measuring)!
Note
:
The SPD has to be removed for testing
(measuring)!
SPD in NH-design
Type
Part No.
Tolerance range
DEHNflex
Type
Part No.
(
Pin L
Þ
N)
DFL E 255
924 387
566
785
485
601
DFL Y 255
924 388
566
785
485
601
DFL A 255
924 389
566
785
485
601
DFL D 255
924 395
566
785
485
601
(
Pin N
Þ
PE)
Page
26
LLV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
ULV
in [ V ]
(
Pin 1
Þ
Pin 2)
®
LLV
in [ V ]
ULV
in [ V ]
Tolerance
range
®
LLV
in [ V ]
ULV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
**Repeat test with reverse polarity,
if the first measured value is too high!
LLV
in [ V ]
ULV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
V NH00 280
900 261
387
478
VA NH00 280
900 262
755
1059
V NH00 280 FM
900 263
387
478
VA NH00 280 FM
900 264
755
1059
V NH1 3 280
900 265
387
478
VA NH1 3 280
900 266
760
1042
V NH1 280
900 270
387
478
VA NH1 280
900 271
755
1059
Tolerance range
LLV
in [ V ]
ULV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
Tolerance range
Tolerance range