9
Publication No. 1637/ UPDATE
07
.1
9
Mat-No. 3003103
„S“
Note:
An additional connection to the equipotential bonding
system at the lower metal part of the supporting tube
system is not required. The rod clamp at the
air-termination mast 30 (tripod) has no function and
does not have to be connected.
Subsequently, fix the conductors in the lower end of the supporting tube system by means metal cleats.
For
this purpose, the dark grey outer sheath of the
HVI
light Conductor
must be removed where the
conductor
is fixed at the cleat so that the black semiconductive sheath can be contacted (see Fig. 3.1.1a,
page 9 and Fig. 3.1.1b, page 10). Ensure that this black sheath is not damaged. The four
HVI
light
Conductors
are
contacted via the cleats fixed at the fixing ring and tightened by means of the eight
M6
slotted head screws using a tightening torque of
5 Nm
(see Fig. 3.1, page 9 and Fig. 3.2, page 10).
Finally attach the cable ties included in the mounting material to fix the conductors on the supporting
tube.
2x
M8
hexagon
lock nut
No electrical,
conductive or earthed
parts may be located
in this adjustment
area, the separation
distance
„s“
must be
maintained!
M8
hexagon lock screw;
15 Nm
fixing ring
Fig. 3.1
Air-termination masts 30 with
HVI
light Conductor
4 x cleat with 4x 2
M6
slotted head screws;
5 Nm
connecting plate