Note
An additional connection to the equipotential bonding
system at the lower metal end of the supporting tube
system is not required. The double cleat at the
air-termination mast 50 (tripod) has no function and
does not have to be connected.
No electrical,
conductive or earthed
parts may be located
in this adjustment
area, the separation
distance
„s“
must be
maintained!
Fig. 3.2
Air-termination masts 50 with
HVI
light Conductor
4x cleat with 4x 2
M6
slotted head screws;
5 Nm
M8
hexagon lock screw;
15 Nm
connecting
plate
2x M8
hexagon
lock nut
fixing ring
fixing ring